קופסת חיבורים פופ-אפ פלדה ABS לרצפה 18 מקום בצבע אפור
קופסת חיבורים פופ-אפ פלדה ABS לרצפה 18 מקום בצבע אפור
14177 :מק"ט
קופסת חיבורים פופ-אפ דו כיווני מלבנית פלדה ABS לשולחן 18 מקום. ניתן לחבר מגוון מחברי מולטימדיה,תקשורת וחשמל תואמים לגרנד (4.5x4.5 ס"מ). מגיע ללא מחברים. מיועד להטמעה ברצפה,שטי,פרקט וכו´ לקבלת מראה דקורטיבי אחיד וטבעי. צבע: אפור
• More capacity: 8,12,16,24 way 45*45mm modules, or 3 compartments bridges:
• More optional switch & socket: International 45*45mm modules, 86 type, 120 type etc.
• More optional installation: Horizontal, Side-mounting, Side-mounting & Horizontal;
• More optional box: Galvanized box, Stainless steel box and plastic box etc.
• More optional switch & socket: International 45*45mm modules, 86 type, 120 type etc.
• More optional installation: Horizontal, Side-mounting, Side-mounting & Horizontal;
• More optional box: Galvanized box, Stainless steel box and plastic box etc.
Item |
Underfloor Socket |
Model |
14177 |
Material |
ABS, galvanised steel |
Overall Frame & Lid (mm) |
320.5*230.5 |
Compact floor cut-out(mm) |
(305-310)*(210-215)*(76-110) |
Thickness of concavity/Frame lid recess (mm) |
8 |
Installation depth(mm) |
76~110 |
Plug top clearance(mm) |
14~48 |
Available modules |
86*146MM modules or 45*45 modules |
Accessories plates |
90*80mm |
1. Floor box (For concrete floor) Align floor box in centre as delivered. Bend open ears and fix to raw ceiling.
2. Steel armored conduit (For trunking system/Access floor). Bend open perforation in the sides of floor box and insert steel armored conduct.
3. Put under floor box into cut out and adjust height (For raised floor). Put under floor box into hole/location of raised floor. Then move the adjustable screw in clockwise direction until screws are tightened with flooring. lead the lines into plastic bottom box.
4. Installing Heavy current/Data systems Insert heavy current devices from the top and connect from below and snaptabs into the frame; Insert connected data Jacks from below into the plate, Fasten equipped plate accordingly.
5. Connecting and earthing. Connect heavy carrent/Data with the lines which are lead into bottom box. And connect earthing lines of floor cable systems with earthing screw of bottom box torgue>0.4N.m.Verify reliable and safe.
6. Assembly and plug into underfloor box. Inset heavy carrent and low carrent plugs into frame.
7. Single outlet. Lead heavy and low carrent plug cable cord from edge lord outlet lid. Filling stuff and levelling to floor Fill the sunken area of panel neatly with filling stuff according surface material of floor .Adjust wnder floor box height flush over the four levelling screws.